Abstract:±800kV UHVDC is bipolar with two 12-pulse converters in series,and has much more intricate structural arrangement. The basic operation mode and control strategy for the double converters in series are discussed. In this paper,a complete simulation model is built based on the upcoming Yun-Guang ±800kV UHVDC project by PSCAD/EMTDC. The response characteristics of UHVDC transmission system and its controllers are analyzed under the condition such as full-voltage starting in bipolar,taking one of the 12-pulse converters out of/into operation and single-phase ground fault on the inverter side AC system. The test results show that the control strategy of the traditional ±500kV HVDC system can also be used in the UHVDC system. DC current control at rectifier and extinction angle control at inverter can ensure the system to operate steadily during steady state and transient state. Some beneficial results are obtained,such as the control mode,control strategy for the double converter in series,and the operation sequence of taking one converter out of/into operation.