RTDS Simulation on AC/DC Hybrid CSG with the ±800 Kv Yun-Guang UHVDC Transmission System in Operation

张建设,韩伟强,张尧,钟庆
DOI: https://doi.org/10.3969/j.issn.1674-0629.2009.01.008
2009-01-01
Abstract:The ±800 kV Yun-Guang UHVDC transmission system will be in operation, monopolar in 2009 and bipolar in 2010. Then China Southern Power Grid (CSG) will be more complex and its AC/DC hybrid characteristic will be more notable. This paper builds up the pure electromagnetism transient Real-Time Digital Simulator (RTDS) model of AC/DC hybrid systems for CSG in 2010, and performs simulation analysis on it. The results show that the 0.6 Hz oscillation may occure in CSG when the Yun-Guang UHVDC transmission system is in rated-power operation with the island operation mode. The ocillation can be restrained by reducing the transmission power of the Yun-Guang UHVDC system. Bipolar blocked fault occured in the Yun-Guang UHVDC system may make CSG lose stability, thus it is necessary to explore in advance appropriate security and stability strategies to stand against it.
What problem does this paper attempt to address?