Analysis of Influencing Factors on Thermal Response Test in Ground Source Heat Pump

王沣浩,颜亮,冯琛琛,王新轲
2012-01-01
Abstract:A three dimensional numerical model of ground source heat pump system was established, and the effects of testing time, starting time, borehole radius, initial ground temperature and heat injection rate on identified thermal conductivity of the deep ground soil were analyzed based on the numerical model. The simulation results showed that the identified thermal conductivity decreases with an increase in borehole radius based on column-source method. For parameter estimation, the measuring accuracy of the initial temperature of the deep ground soil has greater effect on identified thermal conductivity. The deviations of measured heat conductivities are within 6%~18%.
What problem does this paper attempt to address?