Design Calculation of Two Heat Exchangers of Direct Sewage Source Heat Pump Unit

庄兆意,刁乃仁,张承虎,孙德兴
DOI: https://doi.org/10.3969/j.issn.1673-7644.2012.06.011
2012-01-01
Abstract:The exact and rational design of the sewage fooled refrigerant evaporator and sewage condenser is critical for the safe and efficient operation of the direct untreated sewage source heat pump system(DSSHPS).Based on the flow resistance and heat exchange characteristic of sewage,this paper introduces the design calculation method of the sewage heat exchanger(evaporation in winter and condensation in summer),proposes an optimized design of arrangement of heat exchange tubes,works out the corresponding design program,and gives the design points and essential parameters of sewage heat exchanger based on the actual case.The results show that the sewage side of heat exchange tubes is smooth without any strengthening methods and that improving the sewage velocity not only increases the heat convection coefficient but also restrains the stable value of the fouling thermal resistance.Increasing the sewage flow path can increase the velocity and improve the heat exchange condition,and the optimal flow path number in the sewage evaporator and condenser is 4 and the arrangement row of tubes includes two modes: side-to-side mode and bottom-to-top mode.To improve the total performance of the sewage heat exchanger,the key problems are how to strengthen the coefficient of heat transfer and reduce the fouling thermal resistance in tubes for sewage side.
What problem does this paper attempt to address?