Modeling and Verification of Immersed Sewage Exchanger

曲云霞,黄峰,宫晔
DOI: https://doi.org/10.3969/j.issn.1671-5292.2009.03.030
2009-01-01
Abstract:The corrosion of units or exchangers can be avoided,and exchangers is convenient to clean for sewage source heat pump systems with the immersed sewage heat exchanger.This system was applied widely in china.The author establishes the heat transfer model of the immersed sewage heat exchanger,testifies the accuracy of the model through experimental results,measures transfer coefficients of the exchanger in winter and summer.Experimental results show that the heat transfer number of per unit length is about 100 W/m for this immersed exchanger using the high density polyethylene pipes.
What problem does this paper attempt to address?