Analysis on Torsional Interactions of Turbo-generators

Zhang Fan,Xu Zheng
DOI: https://doi.org/10.3969/j.issn.1003-9171.2006.08.002
2006-01-01
Abstract:The precondition to reduce power systems for SSO study is that there are no torsional interactions between turbine-generator (T-G) sets.But some conclusions about torsional interactions of units have never been validated so far since field tests on turbine-generator units are difficult fo perform.So in this paper torsional interactions of turbine-generator units were studied by time domain simulation.In order to describe the strength of the torsional interactions of the studied units,torsional interaction factor(TIF)was defined and was taken as an index to estimate the existence of torsional interactions of units.Identical turbine-generator units,similar units and non-identical units under various situations were all considered.Furthermore,the effects of parameters such as the strength of the system,the output power of the generator,and the damping of the units on the torsional interactions were investigated.The results show that the torsional interactions sharply decrease with the increasing differences in the mode frequency of the units.And whether the units are identical or not,there are no evident interactions between the units in different stations.Contrarily,the torsional interactions between the identical units in the same station are significantly strong.
What problem does this paper attempt to address?