Modeling the decay of combined chlorine in simulated distribution system

Yuan Yongqin,Shen Shiquan,Xu Gang,Wang Jun,Yu Jian
DOI: https://doi.org/10.3969/j.issn.1002-8471.2009.05.003
2009-01-01
Abstract:A simulated distribution system and jar tests were carried out to model the combine residual chlorine decay process.The influences of different factors,including water temperature,pH initial chlorine concentration and flow rate,on chloramines decay rates were investigated.The result indicates that the chlorine decay constant kt which demonstrates the influence from the pipe wall,is much greater than the chlorine decay constant kb of bulk water itself.The chlorine decay coefficient is in proportion to water temperature and flow rate,and it is in inverse proportion to pH and initial chlorine concentration,and then the model of combined chlorine decay constant with the above-mentioned affecting factors were built.In addition,the increase of bacteria and biofilm is an important influence factor on combined chlorine decay.In order to improve water quality in distribution system,pipe cleaning and disinfecting should be done regularly.
What problem does this paper attempt to address?