Analysis of Capillary-network Applied in the Closed Cooling Tower

Zhang Lixin,Liu Jingnan,Lin Zonghu,Yin Zheng,Fan Zhiyuan,Liu Yue,Chen Yongbao,Li Ruixiong
DOI: https://doi.org/10.3969/j.issn.0253-4339.2013.06.048
2013-01-01
Abstract:In order to solve the frost crack problem in winter and the tube corrosion problem of corrosive medium in closed cooling towers,engineering plastic capillary-network technology is introduced to the tower.A capillary-networked closed cooling tower was designed by theoretical calculation and the performance of real model has been tested.Research indicates that the heat-exchange ability of two capillary-networked closed cooling towers is similar to a normal closed cooling tower's with copper-tubes of the same size.The cost of the heat-exchanger for both towers is almost the same.On account of the capillary-networked closed cooling towers can prevent corrosion,frost crack,foreign matters,and reduce noise.The capillary-networked closed cooling towers have better technical and economic performance.