Analysis and Optimization for Insulation Structure of Contactor Box in Metal Enclosed Switchgear

YU Qingrui,WANG Jiao,LIU Jianfeng,YAN Jing
DOI: https://doi.org/10.3969/j.issn.1001-5531.2012.18.002
2012-01-01
Abstract:In the light of technology status and development requirements of metal enclosed switchgear,insulation structure of contactor box built current transformer on the 40.5kV products was analyzed,and the optimization scheme was introduced.Weakness of insulation was found out with a power-frequency withstand voltage test,and the distribution of electric field was calculated by Ansoft Maxwell 12.1 software.On the basis of above works,the insulating structure of contact box was improved to meet technical demand.The experimental results show that the optimization design of insulation performance meet the requirements.