New Evaluation Method for XLPE Cable Moisture Content

SHI Ji-kang,HU Wei-jin,CUI Hao,HUA Jia-cheng,HUANG Jian-tao,AI Qian
2013-01-01
Abstract:XLPE cables are vulnerable to the impact of the operating environment and their main insulation is liable to get damp.The damp cables,if used as the middle joints,will reduce the quality of the cable joints and shorten the operating life.In this research,5 kinds of XLPE cables of different thickness and voltage classed were selected as study subjects,and the electric conductivity changes of the damp old cable's main insulation layer were studied at different drying times.By comparing with the conductivity of the new cable of same type,it is concluded that conductivity can be the standard of XLPE cable moisture content,and damp XLPE cables can be dried by heating to restore its insulation level.Finally,the heating and drying processing time required by the five kinds of cables is defined respectively.
What problem does this paper attempt to address?