Measuring moisture content in transformer oil using CAV424

Wang Xianfeng,Shi Dong
DOI: https://doi.org/10.3969/j.issn.1002-7300.2007.06.055
2007-01-01
Abstract:Recently,there is an increasing interest in using transformer-monitoring systems.One of the key variables to be monitored is moisture content in oil,because moisture has a high influence both on transformer electrical and mechanical strength.In this paper,the discussion of the existing methods of water monitoring of oil is presented and mainly the measuring principle based on variable-dielectric-constant capacitive sensor is analysed.Besides,a new high precision capacitance/voltage converter CAV424 has been proposed in order to measure the water content in transformer oil,its principle is also introduced in detail,and the practical application circuit on the basis of CAV424 is designed and analyzed.By analyzing the experimental data,it is found that CAV424 has higher precision and practical value.
What problem does this paper attempt to address?