Application of Inductive Air Jet to Underground Garage for Reducing Both Surface Condensation and CO Pollution in Hot and Humid Climate

GAO Jun,SONG Tianheng,FANG Yanbing,CHEN Ming
DOI: https://doi.org/10.3969/j.issn.0253-374x.2013.06.012
2013-01-01
Abstract:This study tries to resolve the serious condensation problem of a large underground garage with the deeply spatial pattern in Shanghai,which is ventilated by the dominant effect of uniformly distributed exhausts.Test and analysis of surface condensation are carried out in the originally equipped system.An inductive air-jet system is presented by taking into account the attached effect along wall and impinging effect on the floor.The system is applied to intensifying the air velocity and turbulent level near the surface so as to increase the surface heat transfer and temperature.The surface condensation is comfirmed to be significantly reduced in the hot and humid season by the inductive air jets.Meanwhile,the improved system also reduces the accumulation of concentration of CO gaseous pollution at the breathing zone in the garage.
What problem does this paper attempt to address?