Wind Tunnel Test and Stability Performance Analysis of Super Large Cooling Towers with Gas Flue in Power Plant

KE Shi-tang,ZHAO Lin,ZHANG Jun-feng,GE Yao-jun
2011-01-01
Abstract:In order to research the stability performance of cooling tower with gas flue in Xuzhou power plant,the rigid model and aero-elastic model ofsome super large cooling tower in Tongji TJ-3 wind tunnel are carried out,the parameters taken to calculate the wind-induced stability performance are gained in the test,with the numerical simulation and the post processor the local and whole stability are analysed.It is found that the local stability safety factor is lower than the norm value,so the reinforcement scheme must be adopted;the whole stability critical wind speed is higher than the designed wind velocity,the critical wind speed would reduce 30% when considering the internal suction;the critical wind speed is gradually small with the increase of the moulding board,the value is 119.41 m/s when the moulding board is 100,which is much higher than the maximum wind speed.