Indirect evaporative cooling technology:high-performance application of renewable dry air energy in northwest China

Jiang Yi,Xie Xiaoyun,Yu Xiangyang
DOI: https://doi.org/10.3969/j.issn.1002-8501.2009.09.001
2009-01-01
Abstract:The key to promoting application of evaporative cooling technology in dry regions is to produce chilled water by indirect evaporative cooling technology,to solve the problems of too large space occupied by air ducts and too high energy consumption of fans in conventional indirect evaporative cooling system that uses air as the coolant.Presents the principle of chilled water producing technology by indirect evaporative cooling,testing performances of the unit developed and actual application effects.Reviews the applications of this technology at present and prospects in the future.The outlet temperature of indirect evaporative water chiller units is 16 to 19 ℃,reaching the average value of local outdoor wet-bulb temperature and dew-point temperature,and can be used as the cold source.The indirect evaporative chiller and its system have been promoted to a larger extent in northwest China.
What problem does this paper attempt to address?