GFC Photoacoustic Measurement Method for Fire Products

CHEN Tao,SU Guo-feng,SUN Zhan-hui,CHEN Tao,YANG Rui,YUAN Hong-yong
DOI: https://doi.org/10.3969/j.issn.1001-4888.2005.04.002
2005-01-01
Abstract:Sensitive detection and measurement of evolved gas and smoke are always the important demand in fire research.This paper presented a new non-contact method to meter CO concentration and smoke optical density simultaneously and online based on photoacoustic technology.According to gas filter theory and particle light scattering theory,fire products,including gaseous components and smoke particles,were metered in the measuring path between the infrared light source and the photoacoustic cells.Two photoacoustic cells including one CO gas cell and one reference gas cell were used to work as gas filters.Their photoacoustic signal attenuation during the measurement indicated the light extinction caused by CO absorption and smoke particles extinction respectively.Thus CO concentration and smoke optical density can be obtained by processing the photoacoustic signal using the model established in the paper.Experiments of standard test fires show that this method can realized for the compound measurement of smoke particles and CO gas.