Experiment Investigation on Plate Type Heat Exchanger Used as Indirect Evaporative Cooler

Zhao Zhensheng,Ren Chengqin,Tu Min,Zeng Yang,Wang Huahui
DOI: https://doi.org/10.3969/j.issn.0253-4339.2010.01.045
2010-01-01
Abstract:An experimental investigation was conducted on the performance of a crossflow plate type heat exchanger used as an indirect evaporative cooler.It is found that both the air mass flow rate and the ratio of the mass flow rate have a significant effect on the heat exchanger performance.The clear difference in performance is found for dry and wet conditions due to the great change in the ratio of the heat capacity rate of the two fluids.The experimental results show that the actual friction factor was greater than the theoretical value obtained from the laminar flow equation and the critical Re number was about 1200 under dry condition.In addition,the friction factor under wet condition was 2.5-3 times that under dry condition.