An Experimental Investigation on the Performance Analysis of Two-Stage Desert Cooler

Pushpanjay K. Singh,Sudarshan Singh,Amar Nath Sinha
DOI: https://doi.org/10.1080/01457632.2024.2407671
IF: 2.3
2024-10-05
Heat Transfer Engineering
Abstract:The present experimental investigation reports the performance of both the single and two stage direct evaporative cooling systems in composite climatic conditions of Patna, India. A two-stage direct evaporative cooling system has been designed and fabricated. The first stage of the two-stage cooling system utilizes a heat exchanger designed internally to sensibly cool hot and arid ambient air. The effect of varying the frontal air velocity (0.5–9 m/s) and different saline water concentration (5–10%) on the performance of two stage direct evaporative cooler is investigated. The maximum effectiveness of single and two-stage desert cooler is found to be 0.7 and 0.98 at frontal velocity of 2 m/s and 2.5 m/s, respectively. The performance of the two-stage cooler with tap water is found to be 40% higher than the single stage desert cooler. The effectiveness of single and two stage desert coolers with tap water is found to be in the range of 6–11% and 9.3–14% higher compared to the saline water at salt concentrations of 5–10%, respectively. Moreover, increasing salt concentration leads to reduced relative humidity at the cooler exit, with the two-stage cooler exhibiting 28.5% lower relative humidity than single-stage desert cooler.
engineering, mechanical,thermodynamics,mechanics
What problem does this paper attempt to address?