Harmonic Transmission Characteristic and Suppression of Unbalanced Power System

王科,陈建业,周峰,李启斌
DOI: https://doi.org/10.3969/j.issn.1674-0629.2009.04.004
2009-01-01
Abstract:The characteristics of multi-harmonic sources in unbalanced power system are analyzed with the Yd11 traction transformer of electrified railway as an example, and four types of connection mode were tested to illustrate the interaction among multi-harmonic sources.Four passive power filter schemes are adopted to compensate the unbalanced harmonic component, showing that the scheme with the power filter and the non-linear load being in the same substation and having the same phase has the best filtering effect as the total harmonic distortion of system current reducing to 4.2% averagely, and that with the filter and the non-linear load having the same phase but being in different substations has a good filtering effect as the total harmonic distortion of filtered current reducing to about 5.3%.Meanwhile, the schemes with the filter and the non-linear load having different phases enlarge somehow the harmonic content of specific phase.