Study on harmonic suppression of pumped storage power station with static frequency converter

宿清华,吴国忠,杨成林,杨建军,徐德鸿
DOI: https://doi.org/10.3785/j.issn.1008-973X.2002.06.024
2002-01-01
Abstract:Static frequency converters are always used at pumped storage power station. But when SFC works, it generates lots of harmonics and pollutes the electric power system. In this paper the Chinese Harmonic Standard is investigated. With the example of Tongbo Pumped Storage Power Station, the harmonic of static frequency converter (SFC) is analyzed, and the standards for reference of limitations of 18 kV and 500 kV electric power systems are recommended. A model of Tongbo Pumped Storage Power Station is established by SABER simulation program. Then, a comparison of four schemes of Tongbo Project, six-pulse low voltage structure, six-pulse high voltage structure, twelve-pulse low voltage structure and twelve-pulse high voltage structure, is made through simulation. The results show that the voltage THD and current THD of twelve-pulse structure are smaller than that of six-pulse structure and that twelve-pulse structure can effectively reduce 5 or 7 times harmonics.
What problem does this paper attempt to address?