Breakdown Characteristic of XLPE Cable Insulation with Needle Defect under Damped AC Voltage

Zhou Li,Zhou Fusheng,Wang Shihang,Li Jianying,Li Weiwei
DOI: https://doi.org/10.3969/j.issn.1009-9239.2013.01.014
2013-01-01
Abstract:The variation of breakdown characteristic versus frequency of 10 kV XLPE cable with needle defect was studied in a frequency range of 38.2~173.2 Hz under damped AC(DAC) voltage.The results show that when the frequency ranges from 38.2 Hz to 173.2 Hz,the breakdown voltage under DAC increases with the increase of frequency,and the breakdown voltage attains maximum at about 173.2 Hz.When the frequency is in the range of 173.2~300 Hz,the breakdown voltage under DAC decreases with the increase of frequency.
What problem does this paper attempt to address?