Study on micro-polluted water purification by flat membrane bioreactor

Wu Zhichao,Hua Juan,Wang Zhiwei,Liu Jiangfeng
DOI: https://doi.org/10.3969/j.issn.1673-9108.2007.04.014
2007-01-01
Abstract:Operational characteristics and removal effects of organic substances and ammonium of micro-polluted source water treatment by flat membrane bioreactor were studied with membrane flux 18,25 and 30 L/m2·h.Test results indicated that COD removal rates of the three runs were 78.7%,76.9% and 80.4%,respectively.Effluent COD of the three runs were all lower than 15 mg/L.NH+4-N removal rates of the three runs are 90.4%,87.4% and 92.8%,respectively.Effluent NH+4-N of the three runs were all lower than 0.5 mg/L.UV254 removal rates of the three runs were 27.5%,28.2% and 48.1%,respectively.Test results also showed that there was no notable correlation between EPS concentration of mixed liquor and membrane fouling.The selection of operational flux had significant effects on membrane fouling and operation of flat membrane bioreactor in this study.
What problem does this paper attempt to address?