Research on Adiabatic Capillary Tubes′ Correlation of R134a Unit Air-conditioning

YIN Bin,DING Guo-liang,OUYANG Ti
DOI: https://doi.org/10.3969/j.issn.1005-0329.2007.02.022
2007-01-01
Abstract:A R134a unit air-conditioning with 3.8×0.5 millimeter adiabatic capillary tubes are tested.The length of adiabatic capillary tubes have been changed,the changes of the unit's performance are recorded.The experimental data under twenty operation conditions are used to establish adiabatic capillary tubes' correlation of R134a unit air-conditioning through linear regression.Comparison of the experiment result and the correlation's calculation numerical value shows that the minimum relative error is 1.1%,the maximum relative error is 12.6%,and average relative error is 4.95%.