Optimization of devices for heat recovery from extract air

Wei Jining,Tan Chuan,Yang Gensheng,Xie Qiao,Xie Yu,Han Zongwei,Ding Huiting
2012-01-01
Abstract:The device combines the total heat recovery with heat pump heat recovery,by adding an adjustable air volume bypass duct between the outdoor air duct and extract air duct to decrease condensing temperature so as to improve heat pump performance.Presents the principle chart and air handling process in winter and summer.Develops the mathematical model and performs the optimization of main operating parameters.As the result reveals,addition of the bypass duct can markedly decrease condensing temperature of the heat pump,the optimal design mixture ratio is 0.15,the corresponding COP is 5.4 for the heat pump unit,the performance coefficient of the heat recovery device is 11,and there exists an optimal mixture ratio in different outdoor air conditions.