Impact of Wind Farm Integration on Relay Protection(5):Impact of Wind Farms Dispersedly Connected to Distribution Network on Current Protection

ZHANG Baohui,GUO Danyang,WANG Jin,HUANG Renmou,WU Weiming,YUAN Huan
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.05.001
2013-01-01
Abstract:The analysis of fault simulation with electro-magnetic transient model for three kinds of wind power generator shows that,due to the current limitation of its controller,the direct-driven permanent magnetic synchronous generator will not supply big fault current when it is connected to the system with short circuit and its impact on over-current protection can be neglected;the induction generator or doublyfed induction wind power generator,when it is connected to the system,may cause the misoperation of overcurrent protection downstream to the grid-connection point and the refuse-to-trip of over-current protection upstream because of the shortened Ⅱ-zone.The impact of wind power in-feed current or shunt current on short circuit current or the settings of different protection zones is analyzed by changing the grid-connection point,fault location,transmission line length and wind turbine capacity.The curve of short circuit current vs.the short circuit capacity ratio of grid-connection point of wind power shows that,in order to prevent the improper operation of protection,the short circuit capacity ratio of grid-connection point should be less than 10 %.