Improved Design and Field Test of Blocking Filter for Simultaneously Damping Torsional Interaction and Asynchronous Self-Excitation
XIE Xiaorong,DONG Yipeng,LIU Ping,BAI Kai,LIU Hui,WANG Zheng,GAO Xun
DOI: https://doi.org/10.13335/j.1000-3673.pst.2013.03.014
2013-01-01
Abstract:The mechanism of unit asynchronous self-excitation(ASE) caused by blocking filter(BF) installed in Tuoketuo power plant is analyzed,and a method to design improved parameters of BF to suppress ASE and torsional interaction(TI) is researched.Firstly,the influences of BF parameters on ASE and TI modes are analyzed and it is found that increasing resistance in reactance branch of BF or decreasing quality factor of BF reactor is favorable to reduce the risk of ASE,however it will weaken the effect of BF on blocking TI and transient torque to some extent;secondly,a thinking of multi-objective parameter optimization for the improved design of BF is proposed,and based on eigenvalue analysis and optimal search algorithm,by which the divergence of ASE modes under all possible operating conditions can be avoided,the minimum additive resistance is obtained;finally,through field test of a transmission system with series capacitor the improved BF is validated.Test results show that using the improved BF the risk of ASE can be effectively avoided,and under normal conditions the divergence of TI can be prevented,in addition,the consistency between field measurement and simulation analysis is also verified,thus a solid foundation for the secure operation of BF installed in Tuoketuo power plant and series-compensated transmission system is laid.