Suppression Strategy of Ultra-Low Frequency Oscillation in Yunnan Power Grid with BESS

Yixuan Chen,Yuanxiao Zhao,Guangchao Geng,Quanyuan Jiang,Wenlong Liu,Lingfang Li
DOI: https://doi.org/10.1109/naps46351.2019.9000236
2019-01-01
Abstract:Many problems related to power system frequency have occurred in Yunnan Province ─a province in southwestern China with high proportion of hydro-turbine generators. Yunnan Power Grid is a typical direct-current (DC) sending grid and the installed capacity of hydro-generators has accounted for more than 70% of the total capacity after asynchronous interconnection between Yunnan Power Grid and China Southern Power Grid in 2016. But the high hydropower proportion of Yunnan Power Grid makes ultra-low frequency oscillation (ULFO) more prone to occur. Battery Energy Storage System (BESS) has broad application prospects in frequency regulation. Aiming at the ULFO problem caused by AGC daily operation, a coordinated AGC strategy based on BESS is proposed. It is able to eliminate ULFO caused by AGC action by ramping the AGC signal assigned to the units and self-adaptive action of BESS with a small energy storage capacity once the system is judged to be at risk of oscillation. The effectiveness of the proposed method is verified using real-world data from Yunnan Power Grid in China based on MATLAB\SINMULINK.
What problem does this paper attempt to address?