Stability Analysis of Ultra-Low Frequency Oscillation of Yunnan Power Grid Based on Value Set Approach

ZHOU Jinghao,JIANG Chongxi,GAN Deqiang,HUANG Wei,HUANG Run,WU Chen,ZHANG Jie
DOI: https://doi.org/10.13335/j.1000-3673.pst.2017.1894
2017-01-01
Abstract:This paper presents a multi-parameter graphic-oriented robustness analysis method for ultra-low frequency oscillations based on value set approach. Yunnan Power Grid is taken as a study example, where ultra-low frequency oscillations occurred after asynchronously connected to China Southern Power Grid. Firstly, Yunnan Grid is represented with a uniform-frequency model to catch dynamics of ultra-low frequency oscillations. Value set of the system characteristic polynomial within frequency range is then calculated so that the system robust stability is analyzed by observing distances between the value sets and origin. Effects of uncertain parameters on system stability are analyzed and improvement measures are suggested. Results show that excessive large proportion of hydropower during asynchronous interconnection is a culprit contributing to the ultra-low frequency oscillations in Yunnan Grid. Moreover, turbine parameter coefficients are proved to play an important part in system stability, and should not be overlooked in system modelling. By optimizing parameters of hydropower governors, the stability is improved.