Study on Fault Component Differential Protection for Isolated Power System

HU Dan,ZHANG Xue-min,YUAN Zhao-qiang,WANG Ya-ting,CHEN Yi-ni
DOI: https://doi.org/10.3969/j.issn.1673-7598.2013.04.003
2013-01-01
Abstract:For the space restriction in isolated power system,the cable is respectively short.To each level cable.the short current to the beginning and end of line is approximately equal over relay.The traditional time current principle can't satisfied the effective protection.By using longitudinal differential protection method,the generators parallel connection system is simulated in PSCAD/ EMTDC and the differential current protection is experimented in MATLAB.The research shows that the fault component differential protection has good ability against transient resistance,which also can distinguish internal and external faults effectively,satisfy the requirements of the elements(line and bus) effective protection.