RESEARCH ON TREATING THE SECONDARY EFFLUENT IN MUNICIPAL WASTEWATER TREATMENT PLANT WITH UF-RO AND ITS UTILIZATION AS THE CIRCULATING COOLING WATER OF POWER PLANT

Zhang Xiuli,Xu Minmin,Li Jing,Gao Guandao
DOI: https://doi.org/10.3969/j.issn.1000-3770.2012.07.017
2012-01-01
Abstract:UF-RO system was used to treat the secondary effluent in municipal wastewater treatment plane with UF utilized as pretreatment process.The results showed that RO membrane had a higher removal ability of inorganic ions,in which the CODMn removal rate and TDS removal efficiency reached 96% and 91%,respectively.The average removal rates of alkalinity,Ca2+,Mg2+,NH4+-N were 90%,98%,98%,90%,respectively.The PO43-removal rate reached 100%,while the average removal efficiencies of SO42-,Cl-were 97%,90%,respectively.Finally the effluent treated by UF-RO could be successfully used as the circulating cooling water of power generation industries based on that major water quality parameters of effluent could meet well standards of the circulating cooling water.
What problem does this paper attempt to address?