Effect of airflow distribution shape on the performance of finned-tube evaporator in air-conditioning
Feng Yongbin,Yan Gang,Qian Wenbo,Tao Kai,Zhang Min
DOI: https://doi.org/10.3969/j.issn.1001-7100.2009.10.007
2009-01-01
Abstract:A distributed parameter model for air-conditioning evaporator has been developed in this paper.The model has been validated by comparing outputs from the model with test data,given in reference papers.The effects of four different velocity fields on the flow and heat transfer of R22 and R290 finned-tube evaporator are comparatively analyzed.The results show that the specific heat load,the mass flow rate and the pressure drop of evaporator under three types velocity field labeled upper triangle,lower triangular and triangular type are all decreasing than that of the uniformity velocity field type.Using the uniformity type as a reference,the upper triangle,lower triangular,and triangular type,all have a lower specific heat load by 7%,4% and 4%,respectively.With differenct velocity fields,the different temperature differences are nearly identical with each other,and the coefficient of heat transfer acts as the dominant factor in the heat transfer process.The mass flow rate of R290 is less than 40% around than that of R22,and the pressure drop is less than 24% around.When the heat flux of the system is contented,R290 has the particular advantages in terms of harmonizing the pressure drop with the mass flow rate and can be used as environment friendly alternative refrigerant for R22 air-conditioning.