Optimal Control Strategy of Supply Air Temperature for VAV Air-Conditioning Systems under Transition Season

晋欣桥,柴小峰,杜志敏
DOI: https://doi.org/10.3969/j.issn.0493-2137.2009.07.004
2009-01-01
Abstract:For variable air volume(VAV)systemsi,t's a key issue to reduce the energy consumption while the indoor air qual-ity(IAQ)remains good.Based on the study of multi-zone building and VAV air-conditioning systems and the requirement of ASHRAE Standard,a supply air temperature(SAT)reset control strategy for the mixing systems was presented and evalu-ated.The performance of outdoor air distribution of multi-zone and energy consumption of systems while using this strategy was analyzed.The results show that SAT is limited by the design capacity of supply air and the damper positions of air condi-tioned zones.When the temperature of outdoor air is lower than the indoor setting valuet,he SAT-reset control strategy can save 2.8% of the daily energy consumption and improve the indoor air quality.