Effect of asymmetrical phase-shift transformer on multi-pulse rectifier

TONG Wei-ming,GAO Lei,WANG Yin-shen
DOI: https://doi.org/10.3969/j.issn.1007-449X.2012.05.011
2012-01-01
Abstract:Asymmetry of phase-shift transformer is the common phenomenon in multi-pulse rectifier.Via analyzing the requirement of multi-pulse rectifier on phase-shift transformer,the types of asymmetry were obtained.Based on the types,the effect of different asymmetry on root mean square(RMS) and phase difference of transformer's output voltage were analyzed.Take delta-connected autotransformer as an example,the effect of primary winding asymmetry on multi-pulse rectifier was analyzed through simulation and experiment.The experimental results show the voltage and current of the system are changed obviously,and the input current contains 5th and 7th non-characteristic harmonics,which will produce pollution to grid if the system operates for long time.