Fast Control Strategy Generation Method Based on Local Information for Prevention of Intertripping

LIU Kun,DONG Xinzhou
DOI: https://doi.org/10.3969/j.issn.1007-290x.2013.03.005
2013-01-01
Abstract:Intertripping caused by flow transferring is an important factor in resulting in blackout all over the world.Effective means to reduce over load degree of non-fault lines and avoid unreasonable action of distant backup protection include measures of fast generator tripping and load shedding.This paper analyzes one example that is to unreasonably cut off non-fault line during the period of open-phase operation of fault line for reason of asymmetrical flow transferring.It proposes one fast generator tripping and load shedding scheme based on local information for prevention of intertripping which is to take recognition result of flow transferring over load as trigger event while the sending end generator tripping and the receiving end load shedding are separately independent of communication which is able to avoid unreasonable cut-off of non-fault lines caused by long-time asymmetrical flow transferring.Simulation verifies feasibility of this scheme.