Study on the Effect of Magnetic Treatment on the Anti-Scaling Function of Blast Furnace Circulating Water

ZHANG Jian-liang,JIANG Li-li,ZUO Hai-bin,YANG Tian-jun,TAN Zan-lin
DOI: https://doi.org/10.13228/j.boyuan.issn1006-9356.2010.11.011
2010-01-01
Abstract:During the production of modern blast furnace,factors which influence longevity of blast furnace concentrate in the cooling system of blast furnace.Adopting proper cooling system and cool water can normally guarantee blast furnace production.This paper studies that under magnetic field strength,current velocity,and time,strong magnetic processing equipment effects PSI index,pH value,the electric conductivity rate for cooling water.Adopting orthogonal experimental,the paper analysis function mechanism of preventing scale.It is found that under the particular condition,exist the best magnetic field strength 26 500 Gs,the best current velocity 0.6 m/s,and the best time 4.5 hours.Applying scanning electron microscopy and X-ray diffraction to scan scale of magnetic and non-magnetic.It indicates magnetic processing makes scale precipitate as aragonite which adhere to pipe weakly.Aragonite presents loose and soft form,suspend in the water,and can easily wash away with water current.This comes to the purpose of preventing scale.
What problem does this paper attempt to address?