Optimal PMU Disposition in Power System Based on Maximal Measurement Tree

孙旻,熊俊杰,张杰,顾伟
DOI: https://doi.org/10.3969/j.issn.1006-6047.2008.08.016
2008-01-01
Abstract:The PMU(Phasor Measurement Unit) disposition based on map topology is studied. With the concept of measurement tree,the rule of searching optimal PMU allocation point is put forward and the disposition method is thus called MMT(Maximal Measurement Tree). It starts from any bus and dispose PMUs to obtain the maximal measurement tree. The MMT simulations are carried out for IEEE 14 - bus system,IEEE 39 - bus system and IEEE 118 - bus system and the results are compared with those of other methods:DFS(Depth First Search),SA(Simulated Annealing) and single - shot which demonstrates that,the number of PMU of MMT is the least and MMT is better in efficiency and convergence speed than SA. The optimal PMU disposition of Jiangxi power system is planned by MMT and single - shot respectively.
What problem does this paper attempt to address?