Research on Combined Measurement Technology for Lightning Voltage and Lightning Current

LI Yan-song,SHEN Wei-hua,ZHU Ling-yu,JI Sheng-chang,WANG Chun-jie
DOI: https://doi.org/10.3969/j.issn.1673-7598.2013.12.001
2013-01-01
Abstract:Referring to the domestic and foreign statistical results,lightning accidents seriously threat the safety of power grid.The research on measurement system for lightning current and lightning overvoltage of high voltage transmission line is of important significance for the lightning protection of the grid.This paper presents a combined measurement technology for measuring lightning current and lightning overvoltage.The current sensor is based on the principle of self-integral mode Rogowski coil.Based on the capacitive voltage divider with self-integral mode,the voltage sensor has a unique electrical structure,in which the aluminum shielding shell of the Rogowski coil is used as one plate of capacitor.To measure the general lightning current of 8/20μs and the impulse current with a rise time of 250ns,the results show the designed Rogowski coil has good frequency response characteristics and a stable sensitivity.The impulse voltage test shows that the voltage sensor and its interface voltage divider circuit can measure the impulse voltages with waveform of 0.5/49μs and 1.2/66μs accurately.The proposed technology meets the demand of lightning measurement.
What problem does this paper attempt to address?