Research on Partial Discharge Breakdown Location Technology of 1000kv GIS in Field Test
Hui Wang,Weijia Yao,Simeng Song,Yiming Zang,Yong Qian,Gehao Sheng
DOI: https://doi.org/10.1088/1742-6596/1486/6/062028
2020-01-01
Journal of Physics Conference Series
Abstract:Abstract During the field test, if the input and output lines and intervals of the withstand voltage test after the GIS equipment are segmented, and a non-self-recovery discharge or breakdown occurs during the test, only the hearing of the human ear will determine the exact location of the failure. It is more difficult, and it is easy for misjudgement to waste manpower, material resources and cause unnecessary damage to equipment. Therefore, in the field AC withstand voltage test of GIS equipment, finding the location of discharge breakdown is a key technical problem that needs to be urgently solved on the site. This paper studies the propagation characteristics and detection principles of electromagnetic wave signals and vibration signals that cause breakdown faults in 1000kV GIS, and develops a positioning system based on combined acoustic-electrical detection technology for AC withstand voltage of UHV GIS in the field. In the test, it was verified through actual test cases that the method can quickly and accurately locate the location of the breakdown discharge, and provided a set of convenient and effective technical means to ensure the smooth on-site withstand voltage test of GIS equipment.