Modeling of Stray Currents From Metro Intruding Into Power System Considering the Complex Geological Conditions in Modern Megacities

Chunmao Li,Qing Du,Yujun Guo,Yijie Liu,Feng Yang,Lu Chen,Xueqin Zhang,Guizao Huang,Guoqiang Gao,Guangning Wu
DOI: https://doi.org/10.1109/tte.2022.3179559
IF: 6.519
2023-03-01
IEEE Transactions on Transportation Electrification
Abstract:The risks of power supply in power systems attributed to stray currents caused by denser metro lines are increasing in modern megacities. Factors such as multi-layered soil and multiple metro operating lines (MOLs) make it more difficult to analyze dc coupling between the metro and power system. This article proposes a model for dc coupling of the metro and power system considering the two systems’ spatial information, the actual multi-layered soil, and the non-linear ionization of soil caused by stray currents. This article presents a dc coupling model suitable for studying multiple metro lines and large-scale power systems in modern megacities, which has an average relative error of 6.3% compared with experimental results. The neutral current of the transformer in a substation is up to 43 A (normal operation requires it to be less than 6 A in amplitude) under the influence of multiple MOL. The non-linear ionization of the soil near the power substations’ grounding network will decrease the soil resistance, this also results in greater dc currents intruding into power substations.
engineering, electrical & electronic,transportation science & technology
What problem does this paper attempt to address?