Study on Explosion Venting Characteristics of L-Type Venting Duct

Fan Wu,Xing Zhou,Yongmei Hao,Sunqi Zhuang
DOI: https://doi.org/10.3390/pr12122726
IF: 3.5
2024-12-03
Processes
Abstract:The failure state of the natural gas pipelines in underground space may cause explosions, and an explosion flow field is affected by the structure of the venting duct. Based on FLACS software v9.0, the influence of the explosion vent and venting duct on temperature and pressure fields is studied. The results show that when the area of the explosion vent increases from 0 to 100 cm2, the peak overpressure decreases by half, and the overpressure drops to zero within 0.3 s. For different L-type venting ducts, when the structural coefficient is less than 5, the peak overpressures and pressure variations are similar. When the structural coefficient is equal to 5, the peak overpressure significantly decreases, and the time to reach the peak value is extended by 50%. From the perspective of achieving a safe and efficient venting effect, the optimal structural coefficient is 5 for the L-type venting duct.
engineering, chemical
What problem does this paper attempt to address?