Source-Independent Fault Detection Method for Transmission Lines in IBR-Dominated Grids

Julio Rodriguez,Isaac Kofi Otchere,Reza Jalilzadeh Hamidi
2024-07-11
Abstract:This paper proposes a source-independent method for the detection and classification of faults along Transmission Lines (TLs). It aims to reduce the protection issues arising from Inverter-Based Resources (IBRs). Inspired by Power Line Communication (PLC), the proposed method utilizes high-frequency carrier waves which are sent from either side of a TL over each phase. As faults disrupt the propagation of carriers, the receiving carrier waves before and during faults exhibit differences. Based on this principle, the proposed method continuously compares the receiving carrier waves with a short history of them to detect and classify faults. The performance of the proposed method was evaluated using EMTP-RV and MATLAB, and compared to traditional phasor-based distance relays. The simulation results confirm the capability of the proposed method in detection and classification of different faults regardless of power sources types.
Applied Physics
What problem does this paper attempt to address?
### Problems Addressed by the Paper The paper proposes a power source-independent method for detecting and classifying faults on transmission lines (TLs), aiming to mitigate protection issues caused by inverter-based resources (IBRs). #### Summary of Main Content - **Background**: With technological advancements and the increasing demand for new power resources, IBRs are being integrated into the grid. Although IBRs have many advantages, their high proportion can negatively impact the grid protection system because IBRs and traditional generators have significant differences in fault response. - **Limitations of Existing Methods**: - Adaptive protection schemes rely on communication, making them susceptible to communication failures and cyber-attacks. - Traveling wave (TWs) protection is highly dependent on grid and fault parameters and needs to be used in conjunction with other protection schemes. - Controlling IBRs to mimic traditional generator fault responses is limited by insufficient energy sources (e.g., solar panels), preventing some IBRs from generating sufficiently high fault currents. - Deploying energy storage devices (e.g., supercapacitors) can solve the problem but is costly. - Time-domain protection methods require precise grid models, and some techniques are still affected by IBRs. - AI-based methods require large datasets for training, making them less feasible for power system applications. #### Proposed New Method - **Principle**: The method is based on the propagation characteristics of high-frequency carrier waves on transmission lines. When a fault occurs, the carrier wave changes at the receiving end, and faults are detected and classified by comparing the carrier waves before and after the fault. - **Advantages**: - High cost and time efficiency, as the required components are similar to those in traditional power line communication (PLC) setups. - Faster response time compared to phasor-based relays. - During installation and commissioning, the output signal strength is sufficient to resist noise, adverse weather, and other interferences. #### Experimental Validation - **Test Case**: Tested in a grid with a fully transposed transmission line of 100 kilometers, 115 kilovolts, and 60 hertz. Simulations were conducted using EMTP-RV and MATLAB, and compared with traditional phasor-based distance relays. - **Results**: Simulation results show that the method can effectively detect and classify various faults (single-line-to-ground fault SLG, line-to-line fault LL, line-to-line-to-ground fault LLG, and three-line-to-ground fault 3LG) under different power source conditions, with detection times within 10 milliseconds. #### Conclusion The study proposes a power source-independent fault detection and classification method that effectively addresses the challenges posed by inverter-based resources (IBRs) to the grid protection system. The method leverages the propagation characteristics of high-frequency carrier waves on transmission lines, offering high practicality and reliability. Future work will further evaluate the method's sensitivity to different influencing parameters (e.g., fault impedance, arc faults, and switching actions).