Single-Ended Fault Location for Hybrid Transmission Line Using Embedded Artificial Intelligence

Rong Yan,Guangchao Geng,Guoqiang Zeng,Quanyuan Jiang
DOI: https://doi.org/10.1109/pesgm40551.2019.8973915
2019-01-01
Abstract:Fault line identification, phase selection, and exact location play a significant role in power system daily protection and maintenance. There is always a trade off between location accuracy and data acquisition cost (e.g., data communication time, measurement equipment cost) using state-of-the-art methods like steady-state phasor-based or traveling wave-based approaches for hybrid transmission line: overhead line combined with cable. The idea of this work is to construct a novel framework summarized as “train in the cloud and infer on the edge”, deploying the fault-location task on the edge of data source for distributed inference instead of sending measured data to a centralized cloud. To archive this goal, a modified long short-term memory (LSTM) network is trained in the cloud, covering various fault scenarios. Meanwhile, the trained model is imported on a small embedded artificial intelligence (e-AI) module equipped in fault recorder of the substation, in order to infer fault information using local single-ended measurements in real time. The performance of the proposed method is tested for various fault scenarios with satisfactory results in real time.
What problem does this paper attempt to address?