A Physics-Informed Data-Driven Fault Location Method for Transmission Lines Using Single-Ended Measurements with Field Data Validation

Yiqi Xing,Yu Liu,Dayou Lu,Xinchen Zou,Xuming He
2023-07-19
Abstract:Data driven transmission line fault location methods have the potential to more accurately locate faults by extracting fault information from available data. However, most of the data driven fault location methods in the literature are not validated by field data for the following reasons. On one hand, the available field data during faults are very limited for one specific transmission line, and using field data for training is close to impossible. On the other hand, if simulation data are utilized for training, the mismatch between the simulation system and the practical system will cause fault location errors. To this end, this paper proposes a physics-informed data-driven fault location method. The data from a practical fault event are first analyzed to extract the ranges of system and fault parameters such as equivalent source impedances, loading conditions, fault inception angles (FIA) and fault resistances. Afterwards, the simulation system is constructed with the ranges of parameters, to generate data for training. This procedure merges the gap between simulation and practical power systems, and at the same time considers the uncertainty of system and fault parameters in practice. The proposed data-driven method does not require system parameters, only requires instantaneous voltage and current measurements at the local terminal, with a low sampling rate of several kHz and a short fault time window of half a cycle before and after the fault occurs. Numerical experiments and field data experiments clearly validate the advantages of the proposed method over existing data driven methods.
Systems and Control
What problem does this paper attempt to address?
The problem this paper attempts to address is: In power systems, most existing data-driven transmission line fault location methods have not been validated with field data, resulting in insufficient accuracy in practical applications. Specifically, on one hand, the fault field data for specific transmission lines is very limited, making it difficult to use for training; on the other hand, if simulation data is used for training, the mismatch between the simulation system and the actual system can lead to fault location errors. Therefore, the paper proposes a data-driven fault location method based on physical information, aiming to extract the range of system and fault parameters by analyzing data from actual fault events, and using these parameters to generate datasets for training, thereby narrowing the gap between simulation and actual power systems. The main contributions of the paper include: 1. Extracting the inherent physical information of the system and estimating the range of system and fault parameters, requiring only single-end measurement data (half-cycle before and after the fault), without the need for the actual fault location. 2. Generating target datasets through simulation that are consistent with the characteristics of field data, greatly expanding the availability of fault datasets with similar characteristics. 3. Validating the effectiveness of the proposed method through field data experiments. Compared to traditional fundamental phasor-based methods, this method only requires a short data window during the fault (half-cycle); compared to the traveling wave method, this method is compatible with the typical sampling rate (several kHz) of digital fault recorders (DFRs) in actual power systems.