Dynamic response characteristics of a controllable CO2 two-phase thermosyphon loop under different regulation modes

Wencheng Wang,Zhen Tong,Hao Wu,Zekun Han
DOI: https://doi.org/10.1016/j.icheatmasstransfer.2024.107311
IF: 6.782
2024-03-01
International Communications in Heat and Mass Transfer
Abstract:In recent years, a two-phase thermosyphon loop (TPTL) with auxiliary devices has been widely studied to improve the application effect of the TPTL in data centers. This paper proposed a controllable CO2 TPTL with valve regulation. The valves were positioned on the riser and downcomer, respectively. Through experimental investigations, the dynamic response characteristics of the TPTL under different regulation modes were thoroughly analyzed. A comparative study of the regulation performance across various modes was conducted. The results demonstrated that valve regulation substantially broadened the normal working load range (NWLR) of the TPTL. Under modes R, D, and RD, the NWLR expanded to 590–1300 W, 340–1300 W, and 340–1300 W, respectively, from the original range of 700–1300 W. Following valve regulation, the temperatures and pressure drops of the TPTL underwent transient changes, with varying amplitudes. Among the three regulation modes, mode D exhibited the most stable dynamic response process and showcased the most effective regulation performance.
thermodynamics,mechanics
What problem does this paper attempt to address?