Defect recognition and condition assessment of epoxy insulators in gas insulated switchgear based on multi-information fusion

Yunjian Wu,Dalin Ding,Yi Wang,Chang Zhou,Haowen Lu,Xiaoxing Zhang
DOI: https://doi.org/10.1016/j.measurement.2022.110701
IF: 5.6
2022-02-01
Measurement
Abstract:Partial discharge (PD) is one of the main reasons of insulation deterioration in power equipment. How to efficiently and accurately recognize as well as assess the PD is an important guarantee for the stable operation of power equipment. Aiming at the problems of low accuracy of single information defect recognition and condition assessment results, the PD experiments about different typical defects of epoxy insulators are carried out in this paper. On this basis, different ultra high frequency (UHF) and ultrasonic feature information are extracted from time resolved partial discharge (TRPD) and phase resolved partial discharge (PRPD) analysis modes. Furthermore, an SDAE-LDDC multi-information fusion algorithm is built to recognize the defect types, with excellent recognition accuracy (over 94%). Based on the pulse current signal, the severity of PD was classified. The feature information that successfully assesses the severity of PD is selected by combining the maximum correlation and minimal redundancy criterion (m-RMR) with support vector machine (SVM). The performance of selected feature information is tested by fuzzy comprehensive evaluation algorithm, and the assessment results of different feature information are combined using the improved Dempster/Shafer (D-S) evidence theory, which improves the accuracy of condition assessment.
engineering, multidisciplinary,instruments & instrumentation
What problem does this paper attempt to address?