Effects of rainfall on the corona characteristics of AC single conductor of 110 kV transmission lines

Qin Hu,Huan Wang,Weiwei Wu,Lichun Shu,Yufan Wu,Xingliang Jiang
DOI: https://doi.org/10.1016/j.epsr.2024.110530
IF: 3.818
2024-09-01
Electric Power Systems Research
Abstract:How to reduce the effect of rainfall on the corona discharge of conductors is a problem that must be considered in the design and operation of transmission lines. This paper takes LGJ-300/40 conductor as the sample, and experimentally investigates the influence of rain conductivity and rainfall intensity on the corona characteristics of AC conductor in multi-functional artificial climate chamber, and analyzes the surface electric field strength distribution of rain-drenched conductor and the vibration and rupture of raindrops. The results show that changing the rain conductivity does not affect the corona characteristics of AC conductor. Compared with the dry environment, the corona inception voltage decreases by 36.94 %∼45.16 % with the increase of the rainfall intensity (from drizzle to rainstorm), and the corona loss and the audible noise increase. The corona loss and the applied voltage satisfy the power function for different rain conductivities (or rainfall intensities), the corona characteristics of the conductor change less in moderate rain and above. The critical rupture electric field strength of water droplets decreases with the increase of raindrop radius. The results of this paper have some reference significance for the selection and design of AC transmission lines.
engineering, electrical & electronic
What problem does this paper attempt to address?