Wrap-around loop pulsating heat-pipe heat exchanger for enhancing the energy efficiency of high-tech cleanroom HVAC systems

Jia-Wei Zheng,Hong-Yi Lin,Chia-Hsing Hsieh,Yu-Lieh Wu,Kai-Shing Yang
DOI: https://doi.org/10.1093/ijlct/ctae013
IF: 2.3
2024-01-01
International Journal of Low-Carbon Technologies
Abstract:Abstract To maintain strict temperature, humidity, and cleanliness requirements, the cleanrooms of high-tech semiconductor fabrication plants have heating, ventilation, and air conditioning (HVAC) systems, which require substantial amounts of energy. To reduce energy consumption, this study proposes using a wrap-around loop pulsating heat pipe (WLPHP) heat exchanger comprising a pulsating heat pipe for precooling high-temperature outdoor air to reduce relative humidity. The heat absorbed by the heat-pipe evaporator is then transferred to the condenser and released, reducing the energy required to subsequently reheat the air with an HVAC system. The experimental results reveal that the system reduces the required reheating energy and increased the moisture removal rate per unit energy consumption by an average of 24.8% and 33% compared with a typical heat exchanger. Hence, using the WLPHP heat exchanger in HVAC systems could provide large energy savings.
energy & fuels,thermodynamics
What problem does this paper attempt to address?
The problem this paper attempts to address is the high energy consumption of heating, ventilation, and air conditioning (HVAC) systems in high-tech cleanrooms (such as semiconductor manufacturing plants, TFT-LCD panel factories, and microelectronics production facilities). These cleanrooms require strict control of temperature, humidity, and cleanliness, resulting in HVAC systems consuming significantly more energy than those in ordinary commercial buildings. To reduce energy consumption, the study proposes a novel Wrapped Loop Pulsating Heat Pipe (WLPHP) heat exchanger for pre-cooling high-temperature outdoor air to lower relative humidity, thereby reducing the energy required for subsequent reheating. Specifically, the paper experimentally investigates the performance of the WLPHP heat exchanger under different inlet air velocities, inlet water temperatures, and inlet water flow rates, and evaluates its application effects in HVAC systems. The research results indicate that using the WLPHP heat exchanger can significantly reduce the energy required for reheating and improve the dehumidification rate per unit of energy consumption, thereby achieving the goals of energy saving and efficiency improvement.