Techno-Economic Evaluation of A Hybrid Hvac System Combining Double-Layer Pipe-Embedded External Wall and Multi-Stage Fresh Air Treatment

Yaxin Zhao,Xianting Li
DOI: https://doi.org/10.1016/j.applthermaleng.2024.124025
IF: 6.4
2024-01-01
Applied Thermal Engineering
Abstract:Double-layer pipe-embedded external wall (DPEW) offers the advantages of load interception and hightemperature cooling/low-temperature heating. However, complete heating, ventilation, and air-conditioning systems using DPEWs and the combination of DPEWs with organized fresh air supply have not yet been investigated. To address this issue, this study proposes a hybrid HVAC system that combines DPEWs and a multi-stage fresh air handling unit (FAHU) utilizing shallow geothermal energy and ground source heat pumps (GSHPs). A dynamic simulation model of the proposed system is developed in TRNSYS software. A comparison of the energy, economic and environmental performance between the proposed system and a reference fan coil system with single-stage FAHU is performed in an office building in Beijing. The results indicate that the cumulative cooling load and cumulative heating load of the proposed system are 42.3 and 60.7 kWh/m2, respectively. The proposed system utilizes shallow geothermal energy to handle 18 % of the cumulative cooling and heating loads, and hightemperature chilled water/low-temperature hot water provided by an efficient GSHP to handle 60 % of the cumulative cooling and heating loads. The proposed system consumes 5.8 kWh/m2 electricity in summer and 12.1 kWh/m2 electricity in winter, and achieves 30% annual energy savings compared with the reference system while maintaining the same level of thermal comfort. The discounted payback period of the proposed system is 3.3 years. The CO2 emissions can be reduced by 4.8 kg/m2 annually by implementing the proposed system. This study provides theoretical support and data basis for the design and operation of DPEW systems.
What problem does this paper attempt to address?