Experimental Study on the Efficiency of Dodecafluoro-2-Methylpentan-3-One on Suppressing Large-Scale Battery Module Fire

Lin Zhang,Fumeng Ye,Yongqi Li,Man Chen,Xiangdong Meng,Jiajia Xu,Jinhua Sun,Qingsong Wang
DOI: https://doi.org/10.1007/s10694-022-01322-2
IF: 3.605
2022-10-10
Fire Technology
Abstract:Currently, it is significant to study the fire suppression of battery modules in energy storage stations. In this work, the combustion tests of a single cell and battery module were conducted on the 243 Ah lithium iron phosphate battery. Meanwhile, the fire extinguishing effect of C 6 F 12 O on large-scale battery module fire was verified under a real-scale fire scenario. Results show that the thermal runaway process of a single cell can be divided into four stages. The thermal runaway process had an "incubation period" in stage II, which was suitable for early warning and fire extinguishing. Thermal runaway can propagate within the battery body and the thermal runaway propagation time was 121 s. Thermal runaway propagation can occur in the battery module, which is much more aggressive and risky than a single cell. It needed around 50 kJ to 60 kJ to support the thermal runaway propagation between an adjacent cell in the battery module. Furthermore, The C 6 F 12 O has good fire extinguishing and cooling effect, which can successfully inhibit the thermal runaway propagation in the battery module. Meanwhile, when the designed fire extinguishing concentration of C 6 F 12 O is reached in the battery pack, the subsequent battery will not be ignited even if the safety valve is opened.
materials science, multidisciplinary,engineering