What is the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms?

J.L.A. Lans,N.M.C. Mathijssen,A. Bode,J.J. van den Dobbelsteen,M. van der Elst,P.G. Luscuere
DOI: https://doi.org/10.1016/j.jhin.2024.02.007
IF: 8.944
2024-02-01
Journal of Hospital Infection
Abstract:BACKGROUND: The operating room (OR) department is one of the most energy-intensive departments of a hospital. The majority of ORs in the Netherlands have an air handling installation with an ultra-clean ventilation (UCV) system. However, not all surgeries require an ultra-clean operating room.AIM: To determine the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms.METHODS: Lower air volume ventilation effectiveness (VE<sub>Lv</sub>) of a Conventional Ventilation (CV), controlled Dilution Ventilation (cDV), Temperature controlled AirFlow (TcAF) and Uni Directional AirFlow (UDAF) system were evaluated within a 4x4 m measuring grid of 1x1 m. The VE<sub>Lv</sub> was defined as the recovery degree (RD), cleanliness recovery rate (CRR) and air change effectiveness (ACE).FINDINGS: The CV, cDV<sub>Lv</sub> and TcAF<sub>Lv</sub> ventilation systems show a comparable mixing character in all areas (A, B and AB) when reducing the air change rate to 20h<sup>-1</sup>. Ventilation effectiveness decreased when the air change rate was reduced, with exception of the ACE. At all points for the UDAF-2<sub>Lv</sub> and at the center point (C3) of the TcAF<sub>Lv</sub>, higher RD<sub>10Lv</sub> and CRR<sub>Lv</sub> were measured when compared to the other examined ventilation systems.CONCLUSION: The ventilation effectiveness decreased when an ultra-clean OR with an ultra-clean ventilation air supply system was switched to an air change rate of 20h<sup>-1</sup>. Reducing the air change rate in the OR from an ultra-clean OR to a generic OR will reduce the recovery degree (RD<sub>10</sub>) with a factor 10 to 100 and the local air change rate (CRR) between 42%-81%.
infectious diseases,public, environmental & occupational health
What problem does this paper attempt to address?