Experimental Study on the Gas Bubble Temperature Around an Arc Under Insulation Oil

Chenguang Yan,Xian Zhou,Ya Xu,Yifei Wu,Hao Liu,Che Xu,Yuzhou Wei,Shuyou Zhu,Baohui Zhang
DOI: https://doi.org/10.1109/tpwrd.2020.3029447
IF: 4.825
2021-04-01
IEEE Transactions on Power Delivery
Abstract:The internal temperature of a gas bubble caused by a fault arc is a key basic parameter for investigating the bubble behavior and the pressure rise inside oil-filled power equipment. Due to the constraints imposed by the measurement methods and experimental conditions, this temperature has always been estimated as a constant value of 2000 K in past decades. In this letter, we present direct experimental evidence of the gas bubble temperature around an arc. A large oil-filled transformer was reformed and used to conduct arcing fault tests. A sapphire fiber optic infrared thermometer was established and used to detect the internal gas bubble temperature. The experimental results confirm that this internal temperature is not constant but rather varies over a wide range from 2100 K to 1500 K, plummeting with rapid bubble growth and then exhibiting small variations until arc extinction. Furthermore, the bubble growth process throughout the arc duration can be approximately regarded as first polytropic and then isothermal.